Input Voltage: 230V AC nominal (Accepts wide inputs from 110V to 285V under half-load to protect battery lifespan)
Output Waveform: Pure Sine Wave
Batteries: 72V Valve Regulated Lead-Acid (VRLA) system (Uses 12V/9Ah batteries, running with the included external battery pack)
Recharge Time: Approximately 5.5 hours to full capacity
AC Outlets: 7 outlets total — 6 x IEC 60320 C13 and 1 x high-current IEC 60320 C19
Phase: Single Phase input and Single Phase output (1:1)
Dimensions (D×W×H): 425 mm × 425 mm × 336 mm
Net Weight: 45.9 kg
Extended Runtime Capability: Ships with an external battery pack out of the box, and allows scaling by adding up to 4 external battery packs (Model: SRV72BP-9A) for hours of custom backup
High-Draw C19 Port: Features an industrial C19 outlet alongside standard C13 ports to supply power directly to large blade servers or server room Power Distribution Units (PDUs)
Zero Transfer Time: Isolates hardware completely from the electrical grid. It transitions instantly to battery power so critical infrastructure never reboots
Intelligent Network Slot: Equipped with a smart expansion slot to slide in an optional Network Management Card (SNMP) for web-based remote tracking and graceful server shutdowns
High-Efficiency ECO Mode: Minimizes system heat output and cuts utility costs by safely bypassing internal regulation components when power grid conditions are ideal
Automatic System Bypass: Keeps downstream loads active by passing raw grid current through seamlessly if the UPS encounters an extreme internal error or structural overload